In a large building, there are 20 bulbs of 40 W each, 5 bulbs of 100 W each, 5 fans of 80 W each, and 1 heater of 1 kW. The voltage supply is 220 V. The minimum capacity of the main fuse of the building should be

Solution

✅ Correct Option: 1

All appliances are in parallel across 220 V, so the main fuse must carry the current for the total power, I=PVI = \dfrac{P}{V}.

P=20×40+5×100+5×80+1000=800+500+400+1000=2700 WP = 20 \times 40 + 5 \times 100 + 5 \times 80 + 1000 = 800 + 500 + 400 + 1000 = 2700 \text{ W}

I=2700220=12.27 AI = \dfrac{2700}{220} = \boxed{12.27 \text{ A}}